A domestic electrical panel is read from the incomer to the outgoing ways. Each module has a precise role.
The incomer and the main RCD
After the meter and the main switch, a 300 mA RCD monitors the whole installation: it trips if current leaks to earth.
The 30 mA RCDs
More sensitive, they protect the higher-risk circuits: bathroom, washing machine, tumble dryer, dishwasher. Their type (AC, A, F, B) indicates the forms of fault current they detect; electronic appliances require at least type A, a charging point often more.
The breakers
One breaker per circuit. It is marked with a letter and a number, for example C16: the curve (B, C, D) and the rating in amperes. The rating depends on the cable size: 16 A for 1.5 mm², 20 A for 2.5 mm² in common cases.
| Cable size | Max. usual rating | Typical use |
|---|---|---|
| 1.5 mm² | 16 A | Lighting |
| 2.5 mm² | 20 A | Sockets, oven, washing machine |
| 6 mm² | 32 A | Single-phase hob, charging point |
The other modules
Surge protector, day/night contactor, latching relays, timers and modular sockets often complete the panel.